7. Description of Parameters MD500 User Manual
- 218 -
7.11.15 Hibernating and Wakeup
The hibernating and wakeup function is used in the water supply application. Generally, set the wakeup frequency equal to or
higher than the hibernating frequency. If they are set to 0, the function is disabled.
Figure 7-71 Hibernating and wakeup
Frequency
reference
Time
Time
F8-
F8-50
F8-51
Run
F8-52
Stop
F8-50
Wakeup
Hibernating
Wakeup
Function Code Parameter Name Setting Range Default
) Wakeup frequency Hibernating frequency (F8-51) to max. frequency (F0-10) 0.00 Hz
F8-50 Wakeup delay time 0.0s to 6500.0s 0.0s
F8-51 Hibernating frequency +]WRZDNHXSIUHTXHQF\) 0.00 Hz
F8-52 Hibernating delay time 0.0s to 6500.0s 0.0s
During drive running, when the frequency reference is equal to or smaller than F8-51, the AC drive enters the hibernating state
after the delay set in F8-52.
,QWKHKLEHUQDWLQJVWDWHZKHQWKHIUHTXHQF\UHIHUHQFHLVHTXDOWRRUODUJHUWKDQ)WKH$&GULYHZDNHVXSDIWHUWKHGHOD\VHWLQ
F8-50.
When the frequency source is PID, whether to perform PID operation in the hibernating state is determined by FA-28 (Selection of
PID operation at stop).
7.11.16 Current Running Time Reached
Function Code Parameter Name Setting Range Default
F8-53 Current running time 0.0 to 6500.0 min 0.0 min
This function parameter sets the current running time. If the current running time reaches the value set in this parameter, the
digital output terminal set for the function 40 becomes on, indicating that the current running time is reached.
7.11.17 Output Power correction
Function Code Parameter Name Setting Range Default
F8-54 2XWSXWSRZHUFRUUHFWLRQFRHIÀFLHQW 0.00% to 200.0% 100.0%
7KLVIXQFWLRQSDUDPHWHUVHWVWKHRXWSXWSRZHUFRUUHFWLRQFRHIÀFLHQW:KHQWKHRXWSXWSRZHU8LVQRWHTXDOWRWKHH[SHFWHG
value, perform linear correction via this parameter.