MD500 User Manual 9. Peripheral and Options

Ƶ
Description of Terminals and Jumpers
The following table describes the terminals of the MD38IO1.
Type Terminal Terminal Name Function Description
Power supply
+24V-COM
External +24V
power supply
Provide a +24 V power supply to an external unit.
*HQHUDOO\XVHGWRVXSSO\','2WHUPLQDOVDQGH[WHUQDOVHQVRUV
Max. output current: 200 mA
OP1
Digital input
power terminal
&RQQHFWWR9E\WKHMXPSHU-E\GHIDXOW
When applying an external power supply, remove
WKHMXPSHU-WRGLVFRQQHFWWKH23IURP9DQG
connect the OP1 to the external power supply.
Analog input AI3-PGND Analog input 3
Optically-coupled isolation input, supporting differential
voltage input and temperature detection resistance input
Input voltage range: -10 to 10 VDC
Connect the PT100 or PT1000 temperature sensor
Input mode determined by DIP switch S1, multiple
functions not supported simultaneously
Digital inputs
DI6-OP1 Digital input 6 Optically-coupled isolation compatible with dual-polarity inputs
,QSXWUHVLVWDQFHNȎ
9ROWDJHUDQJHIRULQSXWVWR9
DI7-OP1 Digital input 7
DI8-OP1 Digital input 8
',23 'LJLWDOLQSXW
DI10-OP1 Digital input 10
Analog output AO2-GND Analog output 2
Output voltage range: 0 to 10 V
Output current range: 0 to 20 mA
2XWSXWFXUUHQWZLWKUHVLVWDQFHUDQJHWRȎ
Digital output DO2-CME Digital output 2
Optically-coupled isolation, dual-polarity open-collector output
Output voltage range: 0 to 24 V
Output current range: 0 to 50 mA
Note that CME1 and COM are internally insulated, but are
VKRUWHGE\WKHMXPSHU-LQWHUQDOO\5HPRYHWKHMXPSHU
J7 if you need to apply external power to DO2.
Relay outputs
(RELAY2)
PA- PB
Normally-closed
(NC) terminal
Contact driving capacity:
250 VAC, 3 A, Cos f = 0.4
30 VDC, 1 A
PA- PC
Normally-closed
(NC) terminal
RS485
communication

COM
Communication
interface
Modbus-RTU communication input and output terminal, isolated input
CAN
communication
&$1+&$1/
COM
Communication
interface
CANlink communication input terminal, isolated input