3. Electrical Installation MD500 User Manual
- 56 -
3.4 Wiring Checklist
Ĵ No. Item
ƒ 1 Check the received drive to ensure that you receive a correct model .
ƒ 2 Make sure the correct peripheral devices (regen resistor, braking
XQLW$&UHDFWRUÀOWHUDQGEUHDNHUDUHXVHG
ƒ 3 Check the optional cards to ensure that the receiving is correct.
ƒ 4 Check that the mounting method and location meet the requirements.
ƒ 5 Check that the input voltage of the drive is between 323 and 528 V.
ƒ 6 &KHFNWKDWWKHUDWHGPRWRUYROWDJHPDWFKHVWKHGULYHRXWSXWVSHFLÀFDWLRQ
ƒ 7 Connect the power supply to the R, S, T terminals of the drive properly.
ƒ 8 Connect the motor input cables to the U, V, W terminals of the drive properly.
ƒ &KHFNWKDWWKHFDEOHGLDPHWHURIPDLQFLUFXLWFRPSOLHVZLWKWKHVSHFLÀFDWLRQ
ƒ 10 Decrease F0-15 (carrier frequenency) if the motor output cables exceed 50 m.
ƒ 11 Ground the AC drive properly.
ƒ 12 Check that the output terminals and control signal terminals are connected securely and reliably.
ƒ 13 Check whether two motors are driven. If yes, consider whether to add a thermal relay.
ƒ 14 When using regen resistor and braking unit, check whether they are
wired properly and whether the resistance value is proper.
ƒ 15 Check whether inter-phase capacitance is connected and whether the power supply to
the AC drive can be cut off via the overload protection function of the resistor.
ƒ 16 Use STP wires as signal lines.
ƒ 17 Connect the optional cards correctly.
ƒ 18 Ensure to run control cables and power cables separately.