6. Description of Parameters
- 115 -
6
6.2.4 Command Source + Frequency Reference Setting Channel
It is possible to control nal frequency reference through command source + frequency reference
setting channel.
Figure 6-29 Command source + main frequency reference setting channel
0
1
2
3
4
5
6
7
8
9
Final
frequency
reference
Units position
Tens position
F0-02
Hundreds
position
Digital setting
Pulse reference
Multi- reference
Simple PLC
PID reference
Serial comms.
Operating
panel
Terminal I/O
Serial
comms.
AI1
AI2
AI3
No function
0
1
2
F0-27
Units position
Tens position
Hundreds position
Setting
Output
0
0
0
000
0
0
1
0
100
1
0
9
0
900
9
..
.
..
.
..
.
..
.
..
.
Units position
Tens position
Hundreds position
Output
0
0
0
000
0
0
0
1
001
1
0
0
9
009
9
...
...
...
...
...
Units position
Tens position
Hundreds position
Setting
Output
0
0
0
000
0
1
0
0
010
1
9
0
9
090
9
..
.
..
.
..
.
..
.
..
.
Setting
When a command source + frequency reference setting channel is used to control final
frequency reference, both main and auxiliary frequency reference setting channels (F0-03 and
F0-04) become ineffective.
Function Code Parameter Name Setting Range Default
F0-27
Command source +
frequency source
0: No function
1: Digital setting
2: AI1
3: AI2
4: AI3
5: Pulse reference (DI5)
6: Multi-reference
7: Simple PLC
8: PID reference
9: Serial comms.
000
Units position: operating panel (keypad
& display) + frequency reference setting
channel
Tens position: terminal I/O control +
frequency reference setting channel
Hundreds position: serial comms. +
frequency reference setting channel