Common Parameter Settings
‑77‑
Param
eter
Code
Commu
nication
Address
Parameter Name Value Default Unit Change
Mode
A6‑05 0xA605 Parameter
displayed on the
LED operating
panel upon stop
Bit 0: Set frequency (Hz)
0: Hidden
1: Displayed
Bit 1: Bus voltage (V)
0: Hidden
1: Displayed
Bit 2: DI input state
0: Hidden
1: Displayed Bit 3: DO output state
0: Hidden
1: Displayed
Bit 4: AI1 voltage (V)
0: Hidden
1: Displayed
Bit 5: Reserved
Bit 6: Voltage (V) of potentiometer MD‑BP‑
M
0: Hidden
1: Displayed
Bit 7: Count value
0: Hidden
1: Displayed
Bit 8: Length value
0: Hidden
1: Displayed
Bit 9: PLC stage
0: Hidden
1: Displayed
Bit 10: Load speed
0: Hidden
1: Displayed
Bit 11: PID setting
0: Hidden
1: Displayed
Bit 12: Pulse input frequency (kHz)
0: Hidden
1: Displayed
Bit 13: Reserved
Bit 14: Free mapping 0
0: Hidden
1: Displayed
Bit 15: Free mapping 1
0: Hidden
1: Displayed
0x33 ‑ Real time
A6‑07 0xA607 Address displayed
by free mapping 0
0: Invalid address
Others: K connector
0 ‑ Real time