Common Parameter Settings
‑80‑
Param
eter
Code
Commu
nication
Address
Parameter Name Value Default Unit Change
Mode
A6‑22 0xA616 LED default display
check
0: Disable
1: All indicators on the LED operating
panel are steady on.
2: All indicators on the LED operating
panel are off.
3: All indicators on the LED operating
panel blink.
0 ‑ At stop
A6‑36 0xA624 MD‑BP‑M
potentiometer gain
‑10.00 to 10.00 1.00 ‑ Real time
A6‑37 0xA625 Potentiometer MD‑
BP‑M offset
‑10.00 V to 10.00 V 0.00 V Real time
A6‑38 0xA626 Denoising
threshold of
potentiometer MD‑
BP‑M
0.0% to 100.0% 0.1 % Real time
A6‑40 0xA628 Dead zone width of
potentiometer MD‑
BP‑M
0.0% to 100.0% 0.2 % Real time
A6‑41 0xA629 Jump point set by
potentiometer MD‑
BP‑M
‑100.0% to 100.0% 0.0 % Real time
A6‑42 0xA62A Jump amplitude
set by
potentiometer MD‑
BP‑M
0.0% to 100.0% 0.1 % Real time
A6‑43 0xA62B Filter time of
potentiometer MD‑
BP‑M
0 ms to 65535 ms 100 ms Real time
A6‑44 0xA62C Number of filter
times of
potentiometer MD‑
BP‑M
0 to 64 32 ‑ Real time
A8‑00 0xA800 Start/Stop of
background
oscilloscope
0 to 2 0 ‑ Real time
A8‑01 0xA801 Channel 1
parameter
0 to 2000 0 ‑ Real time
A8‑02 0xA802 Channel 2
parameter
0 to 2000 0 ‑ Real time
A8‑03 0xA803 Channel 3
parameter
0 to 2000 0 ‑ Real time
A8‑04 0xA804 Channel 4
parameter
0 to 2000 0 ‑ Real time
A8‑05 0xA805 Sampling interval 1 to 65535 1 ‑ Real time
A8‑06 0xA806 Triggering object A 0 to 2000 1 ‑ Real time