Loading...
Para.
No.
Address
Name
Value Range
Default
Unit
Change
Page
F8-36 63524
Switchover frequency of
deceleration time 1 and
deceleration time 2
0.00 Hz to 655.35 Hz 0.00 Hz At once
F8-36
on page
287
F8-37 63525
Jog preferred
0: Disabled
1: Enabled
0 -
At stop
F8-37
on page
287
F8-38 63526
Zero current detection
level
0.0% to 300.0% 5.0 % At once
F8-38
on page
287
F8-39 63527
Zero current detection
delay
0.01s to 600.00s 0.10 s At once
F8-39
on page
287
F8-40 63528
Output overcurrent
threshold
0.0% to 300.0% 200.0 % At once
F8-40
on page
288
F8-41 63529
Software overcurrent
detection delay
0.00s to 600.00s 0.00 s At once
F8-41
on page
288
F8-42 63530
Detection level of current
1
0.0% to 300.0% 100.0 % At once
F8-42
on page
288
F8-43 63531
Detection width of
current 1
0.0% to 300.0% 0.0 % At once
F8-43
on page
288
F8-44 63532
Detection level of current
2
0.0% to 300.0% 100.0 % At once
F8-44
on page
288
F8-45 63533
Detection width of
current 2
0.0% to 300.0% 0.0 % At once
F8-45
on page
289
F8-46 63534
Timing function
0: Disabled
1: Enabled
0 -
At stop
F8-46
on page
289
F8-47 63535
Timing duration source
0: F8-48
1: AI1
2: AI2
0 -
At stop
F8-47
on page
289
F8-48 63536
Timing duration
0.0 min to 6500.0 min 0.0 min
At stop
F8-48
on page
289
F8-49 63537
AI1 input voltage lower
limit
0.00 V to 655.35 V 3.10 V At once
F8-49
on page
290
F8-50 63538
AI1 input voltage upper
limit
0.00 V to 11.00 V 6.80 V At once
F8-50
on page
290