Commissioning and Trial Run
‑106‑
Parameter
No.
Communication
Address
Parameter Name Setting Range Default Unit Property
FC‑14 64526 Reference 14 ‑100.0% to +100.0% 0.0 % Modifiable
in any states
FC‑15 64527 Reference 15 ‑100.0% to +100.0% 0.0 % Modifiable
in any states
FC‑16 64528 Simple PLC running
mode
0: Stop after running for
one cycle
1: Keep final values after
running for one cycle
2: Repeat after running for
one cycle
0 ‑ Modifiable
in any states
FC‑17 64529 Simple PLC retention
selection upon power
failure
Ones:
0: Non‑retentive upon
power failure
1: Retentive upon power
failure
Tens:
0: Non‑retentive upon stop
1: Retentive upon stop
0 ‑ Modifiable
in any states
FC‑18 64530 Running time of PLC
reference 0
0.0s (h) to 6553.5s (h) 0.0 s (h) Modifiable
in any states
FC‑19 64531 Acceleration/
Deceleration time of
PLC reference 0
0–3 0 ‑ Modifiable
in any states
FC‑20 64532 Running time of PLC
reference 1
0.0s (h) to 6553.5s (h) 0.0 s (h) Modifiable
in any states
FC‑21 64533 Acceleration/
Deceleration time of
PLC reference 1
0–3 0 ‑ Modifiable
in any states
FC‑22 64534 Running time of PLC
reference 2
0.0s (h) to 6553.5s (h) 0.0 s (h) Modifiable
in any states
FC‑23 64535 Acceleration/
Deceleration time of
PLC reference 2
0–3 0 ‑ Modifiable
in any states
FC‑24 64536 Running time of PLC
reference 3
0.0s (h) to 6553.5s (h) 0.0 s (h) Modifiable
in any states
FC‑25 64537 Acceleration/
Deceleration time of
PLC reference 3
0–3 0 ‑ Modifiable
in any states
FC‑26 64538 Running time of PLC
reference 4
0.0s (h) to 6553.5s (h) 0.0 s (h) Modifiable
in any states
FC‑27 64539 Acceleration/
Deceleration time of
PLC reference 4
0–3 0 ‑ Modifiable
in any states
FC‑28 64540 Running time of PLC
reference 5
0.0s (h) to 6553.5s (h) 0.0 s (h) Modifiable
in any states