Commissioning and Trial Run
68
Table 4–2 Drive unit parameters
Parameter
No.
Communication
Address
Parameter Name Setting Range Default Unit Property
F0‑00 61440 G/P type display 1: G type (constant‑torque
load)
2: P type (fan and pump)
Model
dependent
Modification
prohibited
F0‑01 61441 Motor 1 control mode 0: SVC
1: Reserved
2: V/f control
3: Reserved
4: Reserved
5: VC++
2 Modifiable
only at stop
F0‑02 61442 Command source
selection
0: Operating panel of
power supply unit/LCD
panel/Commissioning
software
1: Terminal I/O control
2: Communication control
0 Modifiable
only at stop
F0‑03 61443 Main frequency source
X selection
0: Digital setting (preset
frequency F0‑08, modified
by terminal UP/DOWN,
non‑retentive at power
failure)
1: Digital setting (preset
frequency F0‑08, modified
by terminal UP/DOWN,
retentive at power failure)
2: AI1
3: AI2
4: AI3
5: Reserved
6: Multi‑reference
7: Simple PLC
8: PID
9: Communication setting
10: Reserved
0 Modifiable
only at stop