Commissioning and Trial Run
‑69‑
Parameter
No.
Communication
Address
Parameter Name Setting Range Default Unit Property
F0‑04 61444 Auxiliary frequency
source Y selection
0: Digital setting (preset
frequency F0‑08, modified
by terminal UP/DOWN,
non‑retentive at power
failure)
1: Digital setting (preset
frequency F0‑08, modified
by terminal UP/DOWN,
retentive at power failure)
2: AI1
3: AI2
4: AI3
5: Reserved
6: Multi‑reference
7: Simple PLC
8: PID
9: Communication setting
10: Reserved
0 ‑ Modifiable
only at stop
F0‑05 61445 Base value of range of
auxiliary frequency
source Y for
superposition
0: Relative to maximum
frequency
1: Relative to main
frequency X
0 ‑ Modifiable
in any states
F0‑06 61446 Range of auxiliary
frequency source Y for
superposition
0% to 150% 100 % Modifiable
in any states