Commissioning and Trial Run
70
Parameter
No.
Communication
Address
Parameter Name Setting Range Default Unit Property
F0‑07 61447 Final frequency
reference setting
selection
Ones:
0: Main frequency
reference X
1: Main and auxiliary
calculation result (based
on tens position)
2: Switchover between
main frequency reference
X and auxiliary frequency
reference Y
3: Switchover between
main frequency reference
X and main and auxiliary
calculation result
4: Switchover between
auxiliary frequency
reference Y and main and
auxiliary calculation result
Tens:
0: Main + auxiliary
1: Main auxiliary
2: Max. (main, auxiliary)
3: Min. (main, auxiliary)
4: Main x Auxiliary
0 Modifiable
in any states
F0‑08 61448 Preset frequency 0.00655.35 Hz 50.00 Hz Modifiable
in any states
F0‑09 61449 Running direction 0: Same as default
direction
1: Reverse to default
direction
0 Modifiable
in any states
F0‑10 61450 Maximum frequency 50.00600.00 Hz 50.00 Hz Modifiable
only at stop
F0‑11 61451 Setting channel of
frequency reference
upper limit
0: Set by F0‑12 (Frequency
upper limit)
1: AI1
2: AI2
3: AI3
4: Reserved
5: Communication setting
6: Multi‑speed reference
0 Modifiable
only at stop
F0‑12 61452 Frequency upper limit 0.00655.35 Hz 50.00 Hz Modifiable
in any states
F0‑13 61453 Frequency upper limit
offset
0.00655.35 Hz 0.00 Hz Modifiable
in any states
F0‑14 61454 Frequency lower limit 0.00655.35 Hz 0.00 Hz Modifiable
in any states