- 102 -
4 Parameter Description
4
Parameter
No.
Parameter Name Setting Range Default Unit
Property
F6-42 is used to select program control functions. Each bit of the parameter deīænes a function, as described in
the following table.
If a bit is set to 1, the function indicated by this bit is enabled; if this bit is set to 0, the function is disabled. For
details on how to view and set this parameter, see the descriptions in section 8.21.1.
The functions deīæned by the binary bits of F6-42 are described in the following table.
Bit Function Description Default
Bit0 Reserved - 0
Bit1
Cancelling door open/
close command at delay
after door open/close limit
Bit1 = 1: The door open/close command is cancelled at the delay
of 1s after door open/close limit.
0
Bit2
Not judging door lock
state at door close output
On normal conditions, the system determines that the door is
completely closed only when the door close limit signal is active
and the door lock is applied.
If this function is enabled, the system need not judge the door lock
state.
0
Bit3
Door close command
output during running
The door close command is output continuously during the
elevator running.
0
Bit4
Returning to base īoor
for veriīæcation at īærst-time
power-on
The elevator runs to the bottom īoor for veriīæcation at power-on
for the īærst time.
0
Bit5
Clearing calls immediately
at elevator lock
Bit5 = 1: After the elevator lock signal becomes active, the elevator
clears all car calls and hall calls and lands at the elevator base
īoor.
Bit5 = 0: After the elevator lock signal becomes active, the elevator
clears hall calls and responds to all registered car calls, and then
lands at the elevator base īoor.
0
Bit6 Electric lock NC output
The electric lock has no outputs at door open and has output at
door close.
0
Bit7
E50 fault detection
cancellation
Bit7 = 1: Fault E50 not detected 0
Bit8
Cancellation of door open/
close limit fault detection
The door open/close limit signal is not detected. 0
Bit9
Cancellation of fault
subcode scrolling display
The keypad will not display the fault subcode in scrolling mode. 0
Bit10 Door open energy-saving
In waiting with door open state, the system closes the lamp and
fan within the time in F9-01 after door open limit.
0
Bit11
Independent running
switch for getting away
from parallel control
Valid: When this signal is active, and the independent running
switch is turned on, the elevator disconnects from parallel control
and works in normal running state.
Invalid: The elevator disconnects from parallel control and enters
VIP running state.
1