- 110 -
4 Parameter Description
4
Parameter
No.
Parameter Name Setting Range Default Unit
Property
F8-08 Anti-nuisance function
0: Anti-nuisance function disabled
1: Nuisance judged by load cell
2: Nuisance judged by light curtain
4: Nuisance judged by light-load
signal
0 -
ā
It is the criteria for judging whether nuisance exists.
The values are as follows:
0: Anti-nuisance function disabled
1: Nuisance judged by load cell
A load cell is required. The system judges whether nuisance exists by comparing the load cell data and the
number of car calls.
2: Nuisance judged by light curtain
The system determines that nuisance exists when the light curtain does not act after the elevator stops at arrival
for three consecutive times.
4: Nuisance judged by light-load signal
If the light-load signal is active, the system determines that nuisance exists when the number of car calls is
greater than a certain value.
When the system determines that the elevator is in the nuisance state, it cancels all car calls. In this case, call
calls need to be registered again.
F8-09
Emergency evacuation
operation speed at power
failure
0.020 to F3-11 0.050 m/s
ā
F8-10
Emergency evacuation
operation mode at power
failure
0: Motor not running
1: UPS
2: 48 V battery power supply
0 -
ā
F8-11 Brake apply delay 0.200 to 1.500 0.600 s
ā
F8-12 Fire emergency īoor 2 0 to F6-00 0 -
ā
F8-14 HCB communication rate
Bit4: Energy saving of HCB
communication
0 -
ā
F8-16
Start address of hall call
auxiliary command
0 to 40 0 -
ā
F8-16 is used to set the HCB start address of the back door in opposite door mode.
HCB address of back door = HCB address of front door at the same īoor + F8-16
F8-17 Hall call address check 0 to 1 0 -
ā
Group F9: Time parameters
F9-00
Idle time before returning
to base īoor
0 to 240 10 min
ā
F9-01
Time for fan and lamp to
be turned off
0 to 240 2 min
ā
F9-02 Motor running time limit 0 to 45 45 s
ā
F9-02 is used to set the running time limit of the motor.
In normal running state, if the continuous motor running time in the same direction between two adjacent īoors
exceeds the setting of this parameter but no leveling signal is received, the system will perform protection.
This parameter is mainly used for over-time protection in the case of steel rope slipping on the traction sheave.
If this parameter is set to a value smaller than 3s, it becomes invalid.
F9-03 Clock: year 2000 to 2100
Current
year
YYYY
ā