- 110 -
4 Parameter Description
4
Parameter
No.
Parameter Name Setting Range Default Unit
Property
F8-08 Anti-nuisance function
0: Anti-nuisance function disabled
1: Nuisance judged by load cell
2: Nuisance judged by light curtain
4: Nuisance judged by light-load
signal
0 -
ā˜†
It is the criteria for judging whether nuisance exists.
The values are as follows:
0: Anti-nuisance function disabled
1: Nuisance judged by load cell
A load cell is required. The system judges whether nuisance exists by comparing the load cell data and the
number of car calls.
2: Nuisance judged by light curtain
The system determines that nuisance exists when the light curtain does not act after the elevator stops at arrival
for three consecutive times.
4: Nuisance judged by light-load signal
If the light-load signal is active, the system determines that nuisance exists when the number of car calls is
greater than a certain value.
When the system determines that the elevator is in the nuisance state, it cancels all car calls. In this case, call
calls need to be registered again.
F8-09
Emergency evacuation
operation speed at power
failure
0.020 to F3-11 0.050 m/s
ā˜…
F8-10
Emergency evacuation
operation mode at power
failure
0: Motor not running
1: UPS
2: 48 V battery power supply
0 -
ā˜…
F8-11 Brake apply delay 0.200 to 1.500 0.600 s
ā˜…
F8-12 Fire emergency oor 2 0 to F6-00 0 -
ā˜…
F8-14 HCB communication rate
Bit4: Energy saving of HCB
communication
0 -
ā˜†
F8-16
Start address of hall call
auxiliary command
0 to 40 0 -
ā˜†
F8-16 is used to set the HCB start address of the back door in opposite door mode.
HCB address of back door = HCB address of front door at the same oor + F8-16
F8-17 Hall call address check 0 to 1 0 -
ā˜†
Group F9: Time parameters
F9-00
Idle time before returning
to base oor
0 to 240 10 min
ā˜†
F9-01
Time for fan and lamp to
be turned off
0 to 240 2 min
ā˜†
F9-02 Motor running time limit 0 to 45 45 s
ā˜…
F9-02 is used to set the running time limit of the motor.
In normal running state, if the continuous motor running time in the same direction between two adjacent oors
exceeds the setting of this parameter but no leveling signal is received, the system will perform protection.
This parameter is mainly used for over-time protection in the case of steel rope slipping on the traction sheave.
If this parameter is set to a value smaller than 3s, it becomes invalid.
F9-03 Clock: year 2000 to 2100
Current
year
YYYY
ā˜†