- 53 -
2 System Commissioning
2
2.2.7 Leveling Accuracy Adjustment
There are two leveling accuracy adjustment methods, described as follows:
1. All-oor adjustment
Parameter No. Parameter Name Setting Range Default
F4-00 Leveling adjustment 0–60 30
F4-00 is used to adjust the car stop position at all oors. The setting of F4-00 is effective to all oors.
Increase F4-00 if under-leveling occurs at every oor and decrease F4-00 if over-leveling occurs at
every oor.
3. Single-oor adjustment
Adjust the car stop position at each oor separately by setting group Fr parameters.
Parameter No. Parameter Name Setting Range Default Unit Property
Fr-00 Leveling adjustment function
0: Disabled
1: Enabled
0 -
Fr-01 Leveling adjustment record 1
00000–60060
30030 mm
Fr-02 Leveling adjustment record 2 30030 mm
Fr-20 Leveling adjustment record 20 30030 mm
The owchart of single-oor leveling accuracy adjustment is shown in the following gure.