- 81 -
4 Parameter Description
4
Parameter
No.
Parameter Name Setting Range Default Unit
Property
F3-06
Deceleration end jerk
time
0.300 to 4.000 1.500 s
F3-07
Deceleration start jerk
time
0.300 to 4.000 1.500 s
They are used to set the running curve during deceleration of the elevator.
F3-05 is the acceleration rate of the elevator speed curve(uniform deceleration segment) .
F3-06 is the time for the rate to increase from 0 to the value set in F3-05 in the speed curve (end jerk segment).
The larger the value is, the smoother the jerk is.
F3-07 is the time for the rate to decrease from the value set in F3-05 to 0 in the speed curve (start jerk segment).
The larger the value is, the smoother the jerk is.
Figure 4-2 Running speed curve
t (time)
V (speed)
F3-04
F3-02
F3-03
F3-09
F3-07
F3-05
F3-06
F2-18
F3-00
F3-01
Figure 4-3 Acceleration rate curve
t (time)
a (acceleration rate)
F3-02
F3-05
F3-03 F3-04
F3-06 F3-07
F3-08 Special deceleration rate 0.200 to 1.500 0.900 m/s2
F3-09
Pre-deceleration
distance
0 to 90.0 0.0 mm