Chapter 3 Mechanical and Electrical Installation
- 19 -
Table 3-2 Recommended regen. resistor models
Controller Model Power of Regen. Resistor (W) Resistance of Regen. Resistor (Ω)
NICE-D-A-S0P2 80 W ≥ 250 Ω
NICE-D-A-SOP4 80 W ≥ 200 Ω
NICE-D-A-SOP7 80 W ≥ 150 Ω
3.2.2 Wiring and Description of Control Circuit Terminals
Figure 3-7 Control circuit terminal arrangement
Reserved
Encoder and control
signal input terminal
TA
1
TC1
TB1
TA2
TB2
TC
2
TA3
TC3
TB
3
Door state
output terminal
+24V
PGA
PGB
PGZ
COM
DI1
DI
2
DI3
DI4
DI5
DI6
DI7
DI8
COM
+24V
COM
Table 3-3 Control circuit terminal description
Name Type Mark
Function
Description
Remarks
Door state
output terminal
Relay output
and grounding
TA1/TB1/TC1
TA2/TB2/TC2
TA3/TB3/TC3
Relay output
1. TA-TB: normally closed (NC)
TA-TC: normally open (NO)
Contact capacity:
250 ACV, 3A; 30 VDC, 1 A
2. Insulation voltage class
between contact and control
circuit: 2.5 kVAC