Chapter 6 Description of Function Codes
- 73 -
0: Disabled
1: Enabled
F6-00 = 1 in the prerequisite of F0-02 = 2.
After you press
OPEN
or
CLOSE
, door width auto-tuning is started. The door machine runs with
the close-open-close logic, and stores the door width upon door open limit and locked-rotor.
For details on the operation, see Chapter 4.
Function Code Parameter Name Setting Range Default Min. Unit
F6-01
Door width auto-
tuning speed
0 to F0-04 (Running frequency
under operation panel control)
3.00 Hz 0.01 Hz
It is used to set the running frequency during door width auto-tuning.
Function Code Parameter Name Setting Range Default Min. Unit
F6-02 Low bits of door width pulse 0–9999 0 1
F6-03 High bits of door width pulse 0–9999 0 1
The door width is calculated using the formula:
Door width = F6-03 x 10000 + F6-02
The obtained door width pulses can be modied on the operation panel.
Function Code Parameter Name Setting Range Default Min. Unit
F6-04
Low speed running distance of door
open startup in distance control
0.0%–30.0% 10.0% 0.1%
It records the number of pulses in real time during door open in distance control. When the
number of pulses is equal to or greater than the value (door width x F6-04), the door machine
switches over from door open startup low speed (F3-00) to door open normal speed (F3-03).
Function Code Parameter Name Setting Range Default Min. Unit
F6-05
Door open slow-down point in
distance control
60.0%–90.0% 70.0% 0.1%
It records the number of pulses in real time during door open in distance control. When the
number of pulses is equal to or greater than the value (door width x F6-05), the door machine
switches over from door open startup normal speed (F3-03) to door open ending low speed
(F3-05).
Function Code Parameter Name Setting Range Default Min. Unit
F6-06 Door open limit point in distance control 80.0%–99.0% 96.0% 0.1%
It records the number of pulses in real time during door open in distance control. When the
number of pulses is equal to or greater than the value (door width x F6-06), the door machine
performs related processing of door open limit.