MAIN SUPPLY INPUT: 90 – 240VAC Remove protective cover to gain access to these terminals.
REQUIRED BATTERY: 12Volt 6/12AH Sealed Lead Acid. OBSERVE POLARITY!
OUTPUT TERMINALS: Two parallel terminals provided for convenience, connect to network
devices.
ETHERNET: IEEE 802.3 Compatible 10Base-T interface using copper RJ45 connector.
LCD: Two line LCD with menu for essential status & configuration.
MENU & SELECT/OK: Buttons for navigating the LCD Menus.
INPUT TERMINALS:
INPUT 1: Programmable Input No 1 active when connected to 0V.
INPUT 2: Programmable Input No 2 active when connected to 0V.
OUTPUT TERMINALS:
OUT 1A & 1B: Programmable Volt Free Normally Open Output Max 24V DC 500mA
TXD: RS232 Output Data which can be many baud rates & data streams.
CTS: RS232 Flow Control Input which can be disabled and/or inverted.
STATUS LEDs:
NET: Blue pulsing indicating the Intercall network processor is running.
EARTH* Indicates too low resistance between the network & protective earth.
AC: Yellow to indicate Mains Supply detected.
DC: Green to indicate DC supply is operating within limits.
BATT* Battery backup fault, battery is not charging.
SD* Fault reported by on-board disk.
DISK: Indicates activity read/write to the on-board SD Disk.
*Red LEDs indicate Fault Conditions.
Onboard Fuse: 5Amp 20mm Quick Blow protection for Battery, Charger is current limited.
Installation: Self Contained Surface Mounted Case. (See Below)
Size & Weights: 370mm x 260mm x 110 mm 4.5Kg