Goodrive300-01 inverter for air compressor Function parameters
-53-
Detailed instruction of parameters
inverter goes from P0.03 to 0Hz.
Setting range: 0.0~3600.0s
When the set frequency is in the range of jumping
frequency, the inverter will run at the edge of the
jumping frequency.
The inverter can avoid the mechanical resonance
point by setting the jumping frequency. The inverter
can set three jumping frequency. But this function
will be invalid if all jumping points are 0.
Setting range: 0.00Hz~P00.03 (Max. output frequency)
Jumping
frequency range 1
Jumping
frequency range 2
Jumping
frequency range 3
Bus voltage
pre-protection
function
Bus voltage pre-protection function: 0~3
BIT0:
1: Enable
0: Close (voltage pre-protection function)
Low-voltage
protection
threshold
Setting range of P08.16: 0.0V~2000.0V
Setting range of P08.17: 0.0V~2000.0V
Setting range of P08.18: 0.0~6000.0s
Setting range of P08.19: 0.0~6000.0s
Coast to stop when bus voltage>P08.17 or <
P08.16; Restart automatically when bus voltage is
back to normal and the time defined by P08.18 has
elapsed.
When bus voltage<P08.16+50V, the upper
frequency limit is 1/2 of rated motor frequency.
Operation will be back to normal when bus voltage is
normal and the time defined by P08.19 has elapsed.
Overvoltage
pre-protection
threshold
Low voltage
frequency-limit
running time