Goodrive350 series high-performance multi-function inverter Chapter 6
-155-
Function
code
Name
Detailed parameter description
Default
value
Modi
fy
29: STO action
4863: Reserved
P06.05
Output terminal
polarity selection
This function code is used to set the polarity of
output terminals.
When the bit is set to 0, input terminal polarity is
positive;
When the bit is set to 1 input terminal polarity is
negative.
BIT3
BIT2
BIT1
BIT0
RO2
RO1
HDO
Y
Setting range: 0x00xF
00
P06.06
Y switch-on delay
This function code defines the corresponding delay
of the level variation from switch-on to switch-off.
Y electric level
Y valid
Invalid
Switch on
delay
invalid
Valid
Switch off
delay
Setting range: 0.00050.000s
Note: P06.08 and P06.09 are valid only when
P06.00=1.
0.000s
P06.07
Y switch-off delay
0.000s
P06.08
HDO switch-on
delay
0.000s
P06.09
HDO switch-off
delay
0.000s
P06.10
Relay RO1
switch-on delay
0.000s
P06.11
Relay RO1
switch-off delay
0.000s
P06.12
Relay RO2
switch-on delay
0.000s
P06.13
Relay RO2
switch-off delay
0.000s
P06.14
AO1 output
selection
10: AI1 input value
11: AI2input value
12: AI3 input value
13: Input value of high-speed pulse HDIA
14: Set value 1 of MODBUS communication
15: Set value 2 of MODBUS communication
16: Set value 1 of PROFIBUS\CANopen
communication
17: Set value 2 of PROFIBUS\CANopen
communication
18: Set value 1 of Ethernet communication
19: Set value 2 of Ethernet communication
20: Input value of high-speed pulse HDIB
0
P06.15
Reserved
variables
0
P06.16
HDO high-speed
pulse output
0