Goodrive350 series high-performance multi-function inverter Chapter 6
-156-
Function
code
Name
Detailed parameter description
Default
value
Modi
fy
21: Reserved
22: Torque current (bipolar, 100% corresponds to
10V)
23: Exciting current (100% corresponds to 10V)
24: Set frequency (bipolar)
25: Ramps reference frequency (bipolar)
26: Running speed (bipolar)
27: Reserved
28: C_AO1 from CODESYS (set P27.00 to 1)
29: C_AO2 from CODESYS (set P27.00 to 1)
3047: Reserved
P06.17
Lower limit of
AO1 output
Above function codes define the relation between
output value and analog output. When the output
value exceeds the set max./min. output range, the
upper/low limit of output will be adopted during
calculation.
When analog output is current output, 1mA
corresponds to 0.5V voltage. In different
applications, 100% of output value corresponds to
different analog outputs.
10V (20mA)
0.0% 100.0%
AO
Setting range of P06.17: -100.0%P06.19
Setting range of P06.18: 0.00V10.00V
Setting range of P06.19: P06.17100.0%
Setting range of P06.20: 0.00V10.00V
Setting range of P06.21: 0.000s10.000s
0.0%
P06.18
Corresponding
AO1 output of
lower limit
0.00V
P06.19
Upper limit of
AO1 output
100.0%
P06.20
Corresponding
AO1 output of
upper limit
10.00V
P06.21
AO1 output filter
time
0.000s
P06.22
P06.26
Reserved
variables
065535
0
P06.27
Lower limit of
HDO output
-100.0%P06.29
0.00%
P06.28
Corresponding
HDO output of
lower limit
0.0050.00kHz
0.00kHz