Goodrive350 series high-performance multi-function inverter Chapter 6
-189-
Function
code
Name
Detailed parameter description
Default
value
Modi
fy
P17.10
Estimated motor
frequency
The estimated motor rotor frequency under
open-loop vector condition.
Range: 0.00 P00.03
0.00Hz
P17.11
DC bus voltage
Display current DC bus voltage of the inverter.
Range: 0.02000.0V
0V
P17.12
Digital input
terminal state
Display current digital input terminal state of the
inverter.
000003F
Corresponds to HDIB, HDIA, S4, S3, S2 and S1
respectively
0
P17.13
Digital output
terminal state
Display current digital output terminal state of the
inverter.
0000000F
Corresponds to R02, RO1, HDO and Y1 respectively
0
P17.14
Digital
adjustment
variable
Display the regulating variable by UP/DOWN
terminals of the inverter.
Range: 0.00HzP00.03
0.00Hz
P17.15
Torque reference
value
Relative to percentage of the rated torque of current
motor, display torque reference.
Range: -300.0%300.0% (rated motor current)
0.0%
P17.16
Linear speed
065535
0
P17.17
Reserved
variables
065535
0
P17.18
Count value
065535
0
P17.19
AI1 input voltage
Display input signal of AI 1
Range: 0.0010.00V
0.00V
P17.20
AI2 input voltage
Display input signal of AI2
Range: 0.0010.00V
0.00V
P17.21
HDIA input
frequency
Display input frequency of HDIA
Range: 0.00050.000kHz
0.000
kHz
P17.22
HDIB input
frequency
Display input frequency of HDIB
Range: 0.00050.000kHz
0.000
kHz
P17.23
PID reference
value
Display PID reference value
Range: -100.0100.0%
0.0%
P17.24
PID feedback
value
Display PID feedback value
Range: -100.0100.0%
0.0%
P17.25
Motor power
factor
Display the power factor of current motor.
Range: -1.001.00
1.00