P09 Group PID control
P09.00
When the frequency command selection (P00.06
P00. 07) is 7 or the voltage setting channel
(P04.27) is 6, the running mode of the inverter is
procedure PID controlled.
The parameter determines the target reference
channel during the PID procures.
0:Keypad digital reference(P09.01)
1:Analog channel AI1 reference
2:Analog channel AI2 reference
3:Analog channel AI3 set
4:High speed pulse HDI set
5:Multi-step speed set
6:MODBUS communication set
7~9: Reserved
The setting target of procedure
100% of the setting equals to 100% of the response
of the controlled system.
The system is calculated according to the
value (0~100.0%).
Note:
Multi-step speed reference, it is realized
setting P10 group parameters.
0 ○
P09.01
When P09.00=0, set the parameter whose
value is the feedback value of the system.
The setting range:-100.0%~100.0%
0.0%