Goodrive200 inverters Function codes
Name
Detailed instruction of parameters
Default
value
PID
feedback
source
Select the PID channel by the parameter.
0:Analog channel AI1 feedback
1:Analog channel AI2 feedback
2:Analog channel AI3 feedback
3:High speed HDI feedback
4:MODBUS communication feedback
5~7:Reserved
Note: The reference channel
can not coincide, otherwise, PID can not
control effectively.
0 ○
P09.03
0: PID output is positive: When
exceeds the PID reference
frequency of the inverter will decrease to balance the
or example, the strain PID control during
1: PID output is negative: When
is stronger than the PID reference
frequency of the inverter will increase to balance the
or example, the strain PID control during
The function is applied to the proportional gain
the strength of the whole PID adjuster.
he parameter of 100 means that when the offset of
PID feedback and reference
ng range of PID adjustor is the Max.
integral function and differential
function).
The setting range:0.00~100.00
1.00 ○
P09.05
This parameter determines the speed of PID
adjustor to carry out integral adjustment on th