Goodrive200 inverters Function codes
Name
Detailed instruction of parameters
Default
value
deviation of PID feedback and reference.
When the deviation
of PID feedback and reference is
100%, the integral adjustor works continuously
the time (ignoring the proportional effect
differential effect) to achieve the
(P00.03) or the Max. Voltage (P04.31).
integral time, stronger is the adjustment
Setting range: 0.01~10.00s
P09.06
This parameter determines the strength of the
change ratio when PID adjustor carries out integral
adjustment on the deviation of PID feedback and
f the PID feedback changes 100% during the time,
the adjustment of integral adjustor (
proportional effect and differential effect) is the
Frequency (P00.03) or the Max. Voltage (P04.
Longer the integral time, stronger is the adjusting.
Setting range: 0.01~10.00s
0.00s
This parameter means the sampling cycle of
feedback. The modulator calculates in
he longer the sapling cycle is, the
slower the response is.
Setting range: 0.00~100.00s
0.10s
PID control
deviation
limit
The output of PID system is relative to the maximum
deviation of the close loop reference. A
the diagram below, PID adjustor stops to work during
et the function properly to adjust
the accuracy and stability of the system.
0.0%