Goodrive200 inverters Basic operation instruction
138
Relative parameters list:
Function
code
Name Detailed instruction of parameters
Default
value
P00.01 Run command channel
0:Keypad running command
channel(“LOCAL/REMOT” light off)
1:Terminal running command channel
(“LOCAL/REMOT” flickering)
2:Communication running command
channel (“LOCAL/REMOT” on)
0
P00.11
ACC time 1 0.0~3600.0s
Depend
on model
P00.12
DEC time 1 0.0~3600.0s
Depend
on model
P01.00 Start mode
0:Start-up directly
1:Start-up afte
r DC braking
2: Start-up after speed tracking
0
P01.01
Starting frequency of
direct start
0.00~50.00Hz 0.50Hz
P01.02
Retention time of the
starting frequency
0.0~50.0s
0.0s
P01.03
The braking current before
starting
0.0~50.0s 0.0%
P01.04
The braking time before
starting
0.0s
P01.05 ACC/DEC selection
0:Linear type
1:Reserved
0
P01.08 Stop mode
0:Decelerate to stop
1:Coast to stop
0
P01.09
Starting frequency of DC
braking
0.00Hz~P00.03(the Max. frequency) 0.00Hz
P01.10
Waiting time before DC
braking
0.0~50.0s 0.0s
P01.11
DC braking current
0.0~150.0% 0.0%

Table of Contents