Goodrive200 inverters Function codes
72
Functio
n code
Name
Detailed instruction of parameters
Default
value
Modify
0.000~1.000s
P05.12
Virtual
terminals
setting
E
nable the input function of virtual terminal at the
communication mode.
0:Virtual terminals is invalid
1:MODBUS
communication virtual terminals are
valid
2~4: Reserved
0
P05.13
Terminals
control
running
mode
Set the operation mode of the terminals control
0:2-wire control 1, comply
the enable with the
direction. This mode is widely used. I
t determines
the rotation direction by the defined FWD and REV
terminals command.
1:2-wire control 2Separate
the enable from the
direction. FWD
defined by this mode is the enabling
ones. T
he direction depends on the state of the
defined REV.
2:3-wire control 1; Sin
is the enabling terminal on this
mode, and the running command is caused by FWD
0