Goodrive200 inverters Function codes
81
Functio
n code
Name
Detailed instruction of parameters
Default
value
Modify
6:Output voltage
7:Output power
8:Reserved
9:Output torque
10:Analog AI1 input value
11:Analog AI2 input value
12:Analog AI3 input value
13:High speed pulse HDI input value
14:MODBUS communication set value 1
15:MODBUS communication set value 2
16~30:Reserved
P06.17
L
ower limit of
AO1
output
0.0%
P06.18
Correspondi
ng AO1
output to the
lower limit
0.00V
P06.19
Upper limit of
AO1 output
100.0%
P06.20
The
correspondin
g AO1
output
to the upper
limit
10.00V
P06.21
AO1 output
filter time
0.000s
P06.22
L
ower limit of
AO2 output
0.0%
P06.23
Correspondi
ng AO2
output to the
T
he above function codes define the relative
relationship between the output value and analog
output. When the output value exceeds the range
of
set maximum
or minimum output, it will count
according to the low-limit or upper-limit output.
When the analog output is current output,
1mA
equals to 0.5V.
In different
cases, the corresponding analog output
of 100% of the output value is different.
Please refer
to each application for detailed information.
10 V (20 m A )
0 .0 % 1 00.0%
A
O
Setting range of P06.18 0.00V~10.00V
Setting range of P06.19 P06.17~100.0%
Setting range of P06.20 0.00V~10.00V
Setting range of P06.21 0.000s~10.000s
Setting range of P06.22 0.0%~P06.24
0.00V