Goodrive350-19 series VFD Function parameter list
- 252 -
Function
code
Name
Description
Default
value
Modify
P06.13
Relay RO2
switch-off delay
0.000s
P06.14
AO1 output
selection
0: Running frequency (0Max. output frequency)
1: Set frequency (0Max. output frequency)
2: Ramp reference frequency (0Max. output
frequency)
3: Running speed (0Synchronous rotation speed
corresponding to max. output frequency)
4: Output current (0Twice the VFD rated current)
5: Output current (0 Twice the motor rated
current)
6: Output voltage (01.5 times the VFD rated
voltage)
7: Output power (0Twice the motor rated power)
8: Set torque value (0Twice the motor rated
torque)
9: Output torque (0Twice the motor rated torque)
10: Analog AI1 input value (010V/020mA)
11: Analog AI2 input value(010V)
12: Analog AI3 input value(010V/020mA)
13: High-speed pulse HDIA input value
(0.0050.00kHz)
14: MODBUS communication set value 1 (01000)
15: MODBUS communication set value 2 (01000)
16: PROFIBUS/CANopen/DeviceNet
communication set value 1 (01000)
17: PROFIBUS/CANopen/DeviceNet
communication set value 2 (01000)
18: Ethernet communication set value 1 (01000)
19: Ethernet communication set value 2 (01000)
0
P06.16
HDO high-speed
pulse output
0