Event ID Event name Event description
1501 Meter - Historic
Reverse Flow
Kamstrup Extended Alarm Byte1: Bit 1 = Historic Reverse (Active infocode within the
last 30 days, no matter how long the infocode was active).
1502 Meter - Active
Empty Pipe
Kamstrup Extended Alarm Byte1: Bit 2 = Active Dry (meter is in a current empty pipe
state).
Is an alarm by default.
1503 Meter - Historic
Empty Pipe
Kamstrup Extended Alarm Byte1: Bit 3 = Historic Dry (Active infocode within the last
30 days, no matter how long the infocode was active).
1504 Meter - Active
Burst
Kamstrup Extended Alarm Byte1: Bit 4 = Active burst (meter is currently in a high flow
state outside of the meter parameters).
Is an alarm by default.
1505 Meter - Historic
Burst
Kamstrup Extended Alarm Byte1: Bit 5 = Historic Burst (Active infocode within the last
30 days, no matter how long the infocode was active).
1506 Meter - Encoder
Programming
Kamstrup Extended Alarm Byte1: Bit 6 = Encoder setup has been changed one or
more times since production.
1507 Meter - Active
Leak Alarm
Kamstrup Extended Alarm Byte2: Bit 0 = The meter is in an active leak state.
Is an alarm by default.
1508 Meter - Historic
Leak Alarm
Kamstrup Extended Alarm Byte2: Bit 1 = Historic Leak (Active infocode within the last
30 days, no matter how long the infocode was active).
1509 Meter - Low
Temperature
Alarm
Kamstrup Extended Alarm: Minimum meter temperature detected. Trigger on <36F
indication from Kamstrup meter.
1510 Meter - High
Temperature
Alarm
Kamstrup Extended Alarm: Maximum meter temperature detected. Trigger on >125F
indication from Kamstrup meter.
1511 End of meter life Kamstrup Extended Alarm: The meter is near the end of its expected life.
1512 Register Removal Kamstrup Extended Alarm: The meter register has been tampered with or removed.
1513 Meter - Zero
Consumption
Detected
Kamstrup Extended Alarm: The meter has detected no usage.
1514 Low Pressure
Alarm
Kamstrup Extended Alarm: The meter has detected minimum pressure.
1515 High Pressure
Alarm
Kamstrup Extended Alarm: The meter has detected maximum pressure.
Gen5 500WERTModule Remote Installation Guide B Events and Alarms
December 5, 2022 LDI-0343 REV002 Itron, Inc. Page 41 of 48