34
8g.
8h.
The WHR has a cable and a Perilex plug for the electrical connection. The
connection must comply with NEN 50110 and locally applicable regula-
tions. The unit is not suitable for connection to the three-phase mains.
☞
Inspect the complete installation.
9. Starting up
9.1 Menu structure
The [MENU], [
▼
], [
▲
] and the [OK] keys can be used to select the following programs.
Set timer Menu P1 Menu not in use
Set time delay Menu P2
Set ventilation Menu P3
Set temperature Menu P4
Display status Menu P5
Display malfunction history Menu P6
Reset Menu P7
The menus P1 and P2 are freely accessible while the menus P3 to P7
require an "access code" (352).
Accessing the menus
Order Key Display Description
1Menu P1 Timer
2
▲
P2 Time delays
3
▲
"1 - -" Access code required (352)
4
▲
"3 - -" First numeral of access code
5OK"- 2 -"
6
▲
"- 5 -" Second numeral of access code
7OK"- - 3"
8
▼
"- - 2" Third numeral of access code
9OKP3Ventilation
10
▲
P4 Temperatures
11
▲
P5 Status
12
▲
P6 Malfunction history
13
▲
P7 Reset
Press [MENU] twice to exit the program. If no more keys are pressed, the program
will stop after five minutes and the display will return to the ventilation position.
The exception to this rule is menu P3. A period of thirty minutes applies here.
9.2 Example
Set the central position of the intake fan to 40%.
Order Key Display Description
1Menu P1 Timer
2
▲
P2 Time delays
3
▲
"1 - -" Access code required (352)
4
▲
"3 - -" First numeral of access code
5OK"- 2 -"
6
▲
"- 5 -" Second numeral of access code
7OK"- - 3."
8
▼
"- - 2" Third numeral of access code
9OKP3Ventilation
10 OK P31 Ventilation procedure
11
▲
P35 Select P35
12 OK 50 Current setting
13
▼
40 Select 40
14 OK P35 Saves value 40
15 MENU P3
16 MENU 1 Ventilation position
9.3 Set parameters
P1 Timer: Menu not in use. P2 Time delays
No. Description Min. Max. Default Unit
21 Switch-on delay high position 0 15 5 Minutes
Low voltage input
22 Switch-off delay high position 0 120 30 Minutes
Low voltage input
P3 Ventilation
No. Description Min. Max. Default Unit
31 Exhaust fan low position 15 98 30 %
32 Exhaust fan medium position 16 99 50 %
33 Exhaust fan high position 17 100 90 %
34 Intake fan low position 15 98 30 %
35 Intake fan medium position 16 99 50 %
36 Intake fan high position 17 100 90 %
37 Current exhaust fan position Current value %
38 Current intake fan position Current value %