JABLOTRON FUTURA SYSTEM DESIGN GUIDE
Page 10/16 JABLOTRON LIVING TECHNOLOGY
44..22. . InstallationInstallation
C ondensate drai n connecti onC ondensate drai n connecti on
In the heat exchanger, the exhausted air is cooled by the supplied air causing moisture condensation. The resulting condensed water is drained
towards the siphon. The condensate drain connection is found at the bottom side of the heat recovery unit. A siphon, which is connected to the
sewerage system, must be mounted onto the coupling of the condensate drain connection (HT 32 mm (1.26") drain pipe).
C ondensate must be al l owed to f r eel y f l ow out of the heat rec over y uni t by gravi ty !C ondensate must be al l owed to f r eel y f l ow out of the heat rec over y uni t by gravi ty !
Rec ommended topol ogy of connecti ng peri pher al s to RS -485 bus Rec ommended topol ogy of connecti ng peri pher al s to RS -485 bus
This RS-485 bus is intended to connect only the peripherals of the Futura heat recovery unit. The bus is four-wire, with a 24 V supply and a
maximum total current of 500 mA. The power supply is resistant to overload or short circuit.
Připojeno
přes
RS485
Montážní krabice JA-190PL
+ rozbočovač JA-110Z-B
O vla d a č e a s e n z o ry C O
Klapky zónovéhotrá - přívod
Předokláda dostupnost v roce
2020 i pro zpětnou doinstalaci.
Klapky zónovéhotrá- odtah
Figure 8: Connection topology
Rec ommended c abl eRec ommended c abl e
Four-wire twisted-pair cable, eg. Unitronic PAAR LiYCY 2 × 2 × 0,34 – 0,5 mm
2
or J-Y(St)Y 2 × 2 × 0,8 mm
2
. It is possible to use UTP or STP cable.
The cable must not run parallel to low or high voltage power lines. Occasional crossing is fine.
B us ter mi nati ng r esi stors RS -485B us ter mi nati ng r esi stors RS -485
The terminating resistor 120R is connected at the heat recovery unit. It is recommended to connect a second terminating resistor at the most
remote controller or sensor. . For more convenient wiring, a Jablotron JA-110Z-B RS-485 bus splitter and JA-190PL box can be used. In the case of
a large number of devices and a long wiring in a star connection, a suitable hub must be used.
Enthal py c ool i ng/heati ng modul e C ool B reezeEnthal py c ool i ng/heati ng modul e C ool B reeze
The CoolBreeze add-on module requires c onnecti on of the outdoor c ondensati on uni t to the mai ns with a f i xed 230V / 50Hz,connecti on of the outdoor condensati on uni t to the mai ns wi th a f i xed 2 30V / 50Hz,
ty pe B 16A f use and a 300 mA resi dual c ur r ent ci rcui t breakerty pe B 16A f use and a 300 mA resi dual c ur r ent ci rcui t breaker . Alternatively, preparation for later installation of the CoolBreeze
module can be made.
The internal evaporator of the CoolBreeze module is connected to the outdoor unit with a 4 x 0.7 5 mm 4 x 0.7 5 mm
22
communication cable. The refrigerant
piping should be 6/10 mm
2
. A minimum coolant pipe length of 5 m (16.4 ft) and no longer than of 15 m (49 ft) must be guaranteed.