JIF-2002 WEIGHING INDICATOR&CONTROLLER
61
※Command List Table
Sending Command to
JIF-2002
JIF-2002 response
R Cr Lf
〈READ〉
Sending latest data once (Data format
depends on F202)
Z Cr Lf
〈ZERO〉
JIF-2002 display will ZERO. Z Cr Lf will be
sent by JIF-2002.
T Cr Lf
〈TARE〉
JIF-2002 will go to NET Mode and display
will TARE. T Cr Lf will be sent by JIF-2002.
N Cr Lf
〈NET〉
JIF-2002 will go to NET Mode. N Cr Lf will
be sent by JIF-2002.
G Cr Lf
〈GROSS〉
JIF-2002 will go to GROSS Mode. G Cr Lf
will be sent by JIF-2002.
※If an invalid character is received?Cr Lf will be sent by the JIF-2002
※If the commands are not accepted for any reason:I Cr Lf will be sent
by the JIF-2002
Sending Command to
JIF-2002
JIF-2002 response
BB Cr Lf
<BEGIN BATCHING>
Send back signal “BB”
“BB” an only be received in the Built in
Automatic Program Control Mode
HB Cr Lf
<HALT BATCHING>
Send back signal “HB”
“HB” an only be received in the Built in
Automatic Program Control Mode
RF Cr Lf
<READS FINAL NET>
Sending Final NET weight
If B Cr Lf is send by JIF-2002, that means
batching is still in process.
S Cr Lf
<SETPOINT>
Signal “S Cr Lf” will send back by JIF-2002.
JIF-2002 will send back SET POINT CODE
until totally receive SET POINT CODE data.
SS ×× Cr Lf
<SET SETPOINT>
SS XX Cr Lf will send back by JIF-2002.
JIF-2002 will send back SET POINT values
until totally receive SET POINT values.
RS ×× Cr Lf
<READ SET POINTS>
JIF-2002 receives signal “RS xx Cr Lf”, and
read xx set point value.
SA Cr Lf
<SET ACCESSORIES>
JIF-2002 will send back signal “SA Cr Lf”.
JIF-2002 will send back ZERO band data
until totally receive Zero Band Value.
RA Cr Lf
<READ ACCESSORIES>
JIF-2002 receives signal “RS xx Cr Lf”, and
read xx Zero Band Value.
CC ×× Cr Lf
<CODE CHANGE>
JIF-2002 will send back signal “CCXX Cr Lf”
and send back ZERO band data (F106=3)