SPIDER W40 – Power supply for 2 controllers with battery support
CONNECTOR DEV2 – connection for controller and el. strike
or other controlled device
Max. 0.3 A. Connect 12V DC to
controller, el. strike, other device
(siren...).
Ground. Connect ground to
controller.
Input for el. strike (also controls 2.
relay). Connect ground to el. strike
and O0 from controller.
Input for alarm. Connect ground
from other device (siren...) and O1
from controller (with alarm output).
Input for door status switch.
Connect magnet for door status
and I0 from controller.
Input for push button. Connect
push button and I1 from controller.
Connect RS485 communication
from controller.
Connect RS485 communication
from controller.
Relay – open contact (NO)
CONNECTOR TMP – tamper/alarm shut down connection
ON switch - when connected to
ground power supply turns back
on from “OFF” state
OFF switch – when connected to
ground power supply turns off –
used in connection with alarm
output on REX V9 or with external
tamper switch
Environment
Do not install the power supply on/in a place, where it can come in
contact with water. You must assure good cable joints, protected
against moisture, otherwise corrosion may damage the power
supply. Damage in such cases is not covered by the warranty. You
have to install the power supply in an airy place.
Opening of the housing
There are two holes on each side of the housing. Use an
appropriate size screwdriver and push it in all four holes. When the
lid pops out, gently remove it. Two black screws are supplied for
additional fastening of the lid.
Communication
Ethernet:
Connect the controllers to the computer through your LAN via
Spider’s Ethernet interface. Adjust network settings of the Spider
using the Codeks Device Manager software so that it will function
properly in your network. Please consult Codeks Device Manager’s
manual.
RS485:
If the power supply does not have a built-in Ethernet interface, it
only serves to power devices. Connect RS485 communication from
controllers to one of the communication converter, from the Spider
family: Spider W5-USB, Spider W5-NET, Spider W40+NET and
through it to the computer.
ORDERING CODES
Spider W40
Communication: NET – Ethernet connection
30 W power supply for 2 controllers
with battery support
30 W power supply for 2 controllers
with battery support, Integrated
Ethernet
OTHER
Please read through our warranty and disclaimer statements.
Connection scheme and additional support for the use of this
product can be found on:
http://www.jantar.si/forum/en