REFILL MANUAL FOR 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID
Revision E
Document # DOC181
Issued: May 31, 2011
Revised: June 23, 2020
Figure 3.6 Agent Fill Station
Selector
Control
Knob
Liquid/
Moisture
Indicator
Discharge
Pressure
Gauge
Inlet Pressure
Gauge
Pump Control
Knob
Agent/Nitrogen
Selection Knob
3.5.2 Supply Drum
Because Novec 1230 fluid is a liquid at typical ambient temperatures and pressure, pumping agent from
a supply drum in a closed system can create a vacuum detrimental to the structural integrity of the IBC
container. To counter this effect, ventilated air is filtered into drums using a vent drier employing disposable
or refillable desiccant cartridges. ese materials can be obtained from Drierite Company, Ltd (www.
drierite.com).
e Drierite part numbers for the appropriate cartridges and adapter are listed below.
Drierite 40451 – Disposable cartridge
Drierite 50068 – Refillable cartridge
Drierite 50001 – Drier adapter
Refer to 3M™ Novec™ 1230 Fire Protection Fluid Storage and Handling document 60-5002-0131-8 for
additional information.
3.6 Agent Fill Station
P/N 99168 (See Figure 3.6)
e agent fill station is necessary to pump the liquid agent from the agent supply tank into the empty
cylinder assembly. e station pump requires a dry compressed air supply capable of pressure between 100
and 120 psi (6.89 and 8.27 bar) at a minimum of 13 cubic feet per minute.
Section 3 Fill Components