Page: 18
FM-200® OPERATION, DESIGN, & SERVICE MANUAL
Revision F
Document # DOC102
Issued: February 1, 2009
Revised: 11-Nov-2011
40YE
Section 2 System Description and Components
2.2.5 Discharge Connection Fittings
Fittings are used to connect the discharge outlet to its associated piping system in order to accommodate
dierences in size, outlet connection, and/or orientation between the discharge outlet and discharge piping.
e ttings used vary according the Series valve.
2.2.5.1 Sv Series Fittings
(supplied by installer)
e ttings for the Sv Series
discharge outlet are to be
supplied by the installer. e
suggested tting arrangement
is shown in Figure 2.2.5.1 and
is used to extend the discharge
outlet and facilitate the
attachment of discharge piping.
Elbow outlets may be oriented
in any direction.
2.2.5.2 Mv Series Fittings
(See Figure 2.2.5.2 for P/N)
e ttings for the Mv Series
discharge outlet consist of two 2 in
(50 mm) grooved couplings, one 2 in
(50 mm) grooved elbow, and one 2
in (50 mm) grooved to NPT adapter
arranged as shown in Figure 2.2.5.2.
ese ttings extend the discharge
outlet and allow for connection of 2 in
(50 mm) NPT piping to the 2 in (50
mm) grooved outlet. Elbow outlets
may be oriented in any direction.
Figure 2.2.5.1 Sv Series Fittings
1 1/4” NPT
Elbow
(32 mm)
1 1/4” NPT
Nipple
(32 mm)
1 1/4” NPT
Union
(32 mm)
1 1/4” NPT
Nipple
(32 mm)
Figure 2.2.5.2 Mv Series Fittings
2” Grooved
to NPT Adapter
(50 mm)
P/N 18474
2” Grooved
Coupling
(50 mm)
P/N 18555
2” Grooved
Coupling
(50 mm)
P/N 18555
Shipped with
Cylinder Valve
as part of Anti-
Recoil Safety
Device
2” Grooved
Elbow
(50 mm)
P/N 18551
8.21 in
209 mm
6.0 in
152 mm
Attaching the manual valve actuator to the electric valve actuator when the actuation pin is not fully locked into
the “up” position may cause the cylinder valve to actuate, resulting in potential injury and/or property damage.
e manual valve actuator consists of a brass body, stainless steel actuation pin, and steel safety ring pin.
To discharge the primary cylinder manually, the ring pin is removed and the emergency release button is
depressed forcing the actuation pin in the electric valve actuator to depress the valve core of the cylinder valve.
All other connected cylinders will then open pneumatically. e manual valve actuator is reset by pulling up on
the palm button and inserting the ring pin.