Page: 24
FM-200® OPERATION, DESIGN, & SERVICE MANUAL
Revision F
Document # DOC102
Issued: February 1, 2009
Revised: 11-Nov-2011
40YE
Section 2 System Description and Components
2.4.3 Discharge Manifold
(supplied by installer)
A discharge manifold may be used in a multiple cylinder system to direct the ow of agent from two or more
cylinders into a common pipe. Manifolds are to be supplied by the installer and may be constructed out of
threaded or welded pipe and ttings. When two or more cylinders are grouped together with a common
manifold, they must be of the same size and ll. A manifolded cylinder arrangement must be tted with
a manifold check valve. Suggested manifold dimensions and arrangements are shown in Figure 2.4.3a,
2.4.3b, 2.4.3c, 2.4.3d, and 2.4.3e. Actual manifold size and dimensions must comply with hydraulic ow
calculations derived from the Janus Design Suite® software.
Figure 2.4.3a Suggested Manifold Congurations for 40, 80, and 130 lb Cylinders
14”
(356 mm)
3-1/2”
(88.9 mm)
1/4” (8 mm) SQ. HD. Pipe Plug
2” (50 mm) NPT Pipe Cap
1-1/4” (32 mm) FNPT
Cylinder Connection
2” (50 mm)
MNPT Outlet
36-1/4” (921 mm)
2” (50 mm) Sched. 40 Pipe
3-1/2”
(88.9 mm)
14”
(356 mm)
14”
(356 mm)
1/4” (8 mm) SQ. HD. Pipe Plug
2” (50 mm) NPT Pipe Cap
1-1/4” (32 mm) FNPT
Cylinder Connection
2” (50 mm)
MNPT Outlet
50-1/4” (1276 mm)
2” (50 mm) Sched. 40 Pipe