Page: 32
FM-200® OPERATION, DESIGN, & SERVICE MANUAL
Revision F
Document # DOC102
Issued: February 1, 2009
Revised: 11-Nov-2011
40YE
Section 2 System Description and Components
Table 2.5.1b - Pneumatically Actuated Wafer Valve Dimensions
Valve
Size
Dimensions
A B C D E F
G H
in mm in mm in mm in mm in mm in mm in mm
3 80 18.39 467 4.75 121 8.13 207 6.63 168 10.57 268 1.94 49 8 3/4-10
4 100 21.00 533 5.25 133 9.38 238 7.88 200 13.58 345 2.13 54 8 3/4-10
6 150 25.44 646 6.88 175 12.13 308 10.63 270 17.22 437 2.31 59 12 3/4-10
8 200 32.10 815 8.38 213 15.00 381 13.00 330 21.38 543 2.88 73 12 7/8-9
Figure 2.5.1c Series 830 Pneumatically Actuated Wafer Valve
Number of Holes = G
Thread Size Thru = H
D
C
B
A
F
E
Figure 2.5.1.1 Valve Solenoid
2.5.1.1 Valve Solenoid
Refer to Table 2.5.1.1 for P/N (See Figure 2.5.1.1)
A solenoid is tted to the selector valves at the pneumatic actuation port to prevent pilot pressure from
actuating the valve until receiving a signal from the re control panel. e solenoid has a NEMA 4 enclosure
with a 1/4 in (8 mm) inlet and 1/8 in (6 mm) exhaust. e solenoid has a standard voltage of 24 VDC or an
optional voltage of 120 VAC 60 Hz (110/50). Additional voltages such as 240 VAC 60 Hz and 12 VDC are
available. It consumes 6.9 watts AC and 6.3 watts DC.
Table 2.5.1.1 - Valve Solenoids
P/N Solenoid Type
99807 24 VDC, Weatherproof
99806 120 VAC, Weatherproof
99769 24 VDC, Weatherproof, Explosion-Proof
99768 120 VAC, Weatherproof, Explosion-Proof