Page: 37
FM-200® OPERATION, DESIGN, & SERVICE MANUAL
Revision F
Document # DOC102
Issued: February 1, 2009
Revised: 11-Nov-2011
40YE
Section 3 System Design
3 SYSTEM DESIGN
is section lists the methods and guidelines necessary to properly design an engineered Janus Fire Systems®
FM-200® Fire Extinguishing System.
Note: Janus Fire System® Fire Extinguishing Systems are designed, manufactured, installed and UL listed
and FM approved to deliver a designated quantity of FM-200® in a "not to exceed" 10 second discharge
time. e "Duration of Protection (Hold Time)" as referenced in NFPA 2001, 2012 edition is a function
of the hazard enclosure's (room) integrity and not a function (or capability) of the re suppression systems
referenced in this publication.
3.1 Hazard Analysis
e rst step in designing an engineered FM-200® total ooding system is to identify the unique
requirements of the area to be protected.
3.1.1 Fuel Source
e design specications for the FM-200® system are dependent on the hazard type, so it is rst necessary
to identify the type of hazard to be protected.
Hazard type is classied according to the combustible materials found in an area and may be considered
Class A (wood, paper, cloth, rubber, and many plastics), Class B (ammable liquids and ammable gases),
Class C (energized electrical equipment), or any combination of the three.
NFPA 2001 (2012 edition) requires the minimum design concentration for a Class A surface re to be equal
to 6.7% (7% for FM Approved systems), the minimum extinguishing concentration of heptane.
e minimum design concentration for a Class B re depends on the extinguishing concentration for the
specic fuel type found in the hazard plus a 30% safety factor. e minimum design concentrations for
particular fuels based upon their cup burner extinguishing concentration are listed in Tables 3.1.1a and
3.1.1b in Appendix B.
e minimum design concentration for a Class C re shall be 7.0% (7.8% for FM Approved systems), which
is equal to the extinguishing concentration of Class A fuels times a safety factor of 1.35, in accordance with
NFPA 2001 (2012 edition).
FM-200® design concentrations should be calculated according to the lowest expected ambient temperature
within the protected area. When calculating the concentration levels for normally occupied spaces, the
design concentration for FM-200® must not exceed the NOAEL (No Observed Adverse Eect Level) of
9% at the highest expected ambient temperature as stated in NFPA 2001.