Page: 68
FM-200® OPERATION, DESIGN, & SERVICE MANUAL
Revision F
Document # DOC102
Issued: February 1, 2009
Revised: 11-Nov-2011
40YE
A door fan integrity test should be performed to determine both the estimated leakage rate of FM-200 and
provide the existing vent area in the protected volume. e Janus Design Suite® can provide an estimate
of the vent area required for the amount of FM-200 being discharged. With the combined information,
adjustments can be made to determine additional venting needs for the enclosure.
For more complete information regarding enclosure integrity and venting consideration please consult
Fire Suppression Systems Association Guide to Estimating Enclosure Pressure and Pressure Relief Vent Area for
Applications Using Clean Agent Fire Extinguishing Systems, PRG-01, First Edition, August 2008, NFPA
2001 and Janus Design Suite® FM-200 Calculation Manual.
5.9 Manual
An "as built" instruction and maintenance manual that includes a full sequence of operations and a full set
of drawings and calculations shall be maintained on site.
5.10 Label
Each cylinder is tted with an identication label indicating the ll quantity of FM-200®.
•
•
•
•
•
FILL DATE
Figure 5.10 FM-200® Cylinder Label
Section 5 Commissioning System