Software Version 3.3 Factory Field Upgrade
24-10025-113 Rev. –
19
CK721-A VERSION 3.3 DATABASE DOWNLOAD
After you reconnect the updated CK721-A to the P2000 host (controller is
online), download all databases to the controller. Refer to the P2000 Software
User Manual and the CK721-A Software Release Notes for details.
The controller is now ready for normal operation.
To ensure that the downloaded databases remain in the controller in the case of
a power and battery failure, you may want to invoke the controller’s write to
flash feature. After writing to flash, the controller will reboot. Refer to the
P2000 Software User Manual for details on how to invoke the controller’s
write to flash feature.
NOTE: Always wait at least 5 minutes after the host download has been
completed (that is, after the download queue count goes down to 0), before
performing a write to flash operation.
RE-CONFIGURING THE COMPUTER
After the databases have been downloaded to the controller and the system
appears to be operating normally, re-configure your computer and return it to
its original settings (see Table 1: Computer Settings).
You have finished the firmware upgrade procedure.