FILTER RETAINER
CLIPS MUST BE
ATTACHED TO
SIDES ONLY
HAT
AIRFLOW
AIRFLOW
FILTER CLIPS INSTALLED
FILTER CLIP INSTALLATION
SEE DETAIL A
FLAT SEALING
SURFACE
GASKET SEAL
HEPA FILTER
GASKET SEAL
DETAIL A
HOLDING FRAME
GASKET
TOP
AIRFLOW
AIRFLOW
High-efciency particulate air (HEPA) lters are installed in
hygienic air units when extreme control of discharge airborne
particles is required. These lters are rated on the percentage
of 3 micron size particulates they capture. In order to achieve
the desired ltration success the lter manufacturer checks
each lter for integrity prior to shipment.
For ultimate success, the HEPA filters must be handled
properly, installed correctly and the nal installation veried.
1. HEPA lters must be handled such that neither the air
entering nor the air leaving side of the lters are subjected
to poking pressures. Sharp objects may directly compromise
the ltration media. General concentrated pressure may
compromise the media by forcing it against the internal
aluminum pleat separators.
If unprotected HEPA lters are placed on dirty surfaces prior
to installing them in the AcuAir unit lter frames they become
subjected to unnecessary contamination and possibly long
term hygienic compromise.
2. In order for HEPA ltration to properly control discharge
air particulate count bypass air must be eliminated. AcuAir
HEPA lters include gaskets to seal between the lter and the
lter rack. During the installation process it is important to
verify the cleanliness of both the gasket and the lter frame
to assure a continuous seal.
HEPA lters must be installed with the lter pleats running
vertically. Contrary to the installation of other rigid lters
where vertical pleats are a best practice, for HEPA lters this
orientation is a must.
3. Although the HEPA lter manufacture inspects every HEPA
lter prior to leaving the factory, it is necessary to scan HEPA
lters after installation to verify that there are no pinhole leaks
and no bypass air. Most pinhole leaks and bypass holes can
be repaired in the eld.