EasyManua.ls Logo

Johnson Controls FRICK QUANTUM HD - Page 19

Johnson Controls FRICK QUANTUM HD
125 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
QUANTUM™ HD COMPRESSOR CONTROL PANEL
COMMUNICATIONS SETUP
090.040-CS (JAN 14)
Page 19
The following is a detailed description of each command:
RETURN COMPRESSOR STATUS INFO: #IDI
Command structure:
Command Description
# Start of command sequence
ID Compressor (ID) code (01, 14, etc.)
I Return Status (I)nformation command
Returned Answer, ie: 090RRRN340
Character
Position
Description of returned data
1, 2, 3 Slide Valve position.
4
R = (R)emote
(Slide Valve)A = (A)uto
M = (M)anual
5
R = (R)unning
O = (O)ff
S = (S)lide Valve too high
P = (P)ermissive Start not energized
I = d(I)fferential Pressure too high
T = s(T)opping
X = Au(X) not energized
U = (U)nable to start
6
R = (R)emote
(Compressor
mode)
M = (M)anual
A = (A)uto
7
C = (C)utout (Shutdown)
A = (A)larm
N = (N)ormal
8, 9, 10 Suction value in PSIA.
CR, LF (Carriage Return, Line Feed)
Note: The following control commands are for remote con-
trol of a compressor. A compressor should be in both remote
compressor mode and remote Slide Valve or capacity mode
for remote control.
COMPRESSOR START CONTROL: #IDRID
Command structure:
Command Description
# Start command sequence
ID Compressor (ID) code (01, 14, etc.)
R Sta(R)t compressor command.
ID (ID) code repeated for verification
NOTE: The compressor must be in the remote Start
Mode for this command to be executed.
Returned answer:
Character
Position
Description of returned data
1 (A)cknowledge
2, 3 (ID) code verified
CR, LF (Carriage return, line feed)
COMPRESSOR STOP CONTROL: #IDSID
Command structure:
Command Description
# Start command sequence
ID Compressor (ID) code (01, 14, etc.)
S (S)top compressor command.
ID (ID) code repeated for verification
NOTE: The compressor must be in the remote
Start mode for this command to be executed.
Returned answer:
Character
Position
Description of returned data
1 (A)cknowledge
2, 3 (ID) code verified
CR, LF (Carriage return, line feed)