QUANTUM™ HD COMPRESSOR CONTROL PANEL
COMMUNICATIONS SETUP
090.040-CS (JAN 14)
Page 60
DIGITAL BOARD VALUES: (Read Only)
Frick
®
Address
AB
Address
Modbus
Address
Read/Write Description of Data
Digital
Board #
Channel
#
Module
Type
1001 N10:1 41002 R Oil Level/Oil Switch 1 13 Input
1002 N10:2 41003 R Capacity Decrease 1 6
Output
1003 N10:3 41004 R Capacity Increase 1 5
1004 N10:4 41005 R Volume Decrease 1 8
1005 N10:5 41006 R Volume Increase 1 7
1014 N10:14 41015 R Economizer 1 11
Output
1015 N10:15 41016 R Liquid Injection 1 9
1020 N10:20 41021 R Oil Heater 1 21 Output
1024 N10:24 41025 R Hot Gas Bypass 1 16 Output
1026 N10:26 41027 R Compressor Motor Start Signal 1 1 Output
1027 N10:27 41028 R Compressor Motor Starter Feed-back 1 2 Input
1028 N10:28 41029 R Oil Pump Start Signal 1 3 Output
1029 N10:29 41030 R Oil Pump Feed-back 1 4 Input
1030 N10:30 41031 R Full Flow Pump/Start Signal None 0
Output
1032 N10:32 41033 R Oil Pump #2 Start Signal 2 15
1033 N10:33 41034 R Oil Pump #2 Feed-back 2 16 Input
1036 N10:36 41037 R High Liquid Level Shutdown 1 14
Input1037 N10:37 41038 R Regulator Mode A 1 19
1038 N10:38 41039 R Regulator Mode B 1 20
1042 N10:42 41043 R Shutdown 1 23
Output
1043 N10:43 41044 R Warning 1 22
1044 N10:44 41045 R Balance Piston 1 12
1045 N10:45 41046 R Panel Heater 1 15
1049 N10:49 41050 R Permissive Start 2 17 Input
1050 N10:50 41051 R Ready to Run 2 1
Output1051 N10:51 41052 R Remote Enabled 2 2
1052 N10:52 41053 R Recycle Delay 2 6
1053 N10:53 41054 R Remote Start/Stop 2 3
Input1054 N10:54 41055 R Remote Load 2 4
1055 N10:55 41056 R Remote Unload 2 5
1056 N10:56 41057 R Condenser Control Step 1 2 21
Output
1057 N10:57 41058 R Condenser Control Step 2 2 22
1058 N10:58 41059 R Condenser Control Step 3 2 23
1059 N10:59 41060 R Condenser Control Step 4 2 24
1060 N10:60 41061 R Power Assist 1 24
1061 N10:61 41062 R Dx Circuit #1 2 19
1062 N10:62 41063 R Dx Circuit #2 2 20