QUANTUM™ HD COMPRESSOR CONTROL PANEL
COMMUNICATIONS SETUP
090.040-CS (JAN 14)
Page 96
DBS SETPOINT VALUES:
Frick
®
Address
AB
Address
Modbus
Address
Read/
Write
Description of Data Units
8950 N119:50 48951 R Average Current Amps
8951 N119:51 48952 R Elapsed Run Time Hours Hours
8952 N119:52 48953 R Elapsed Run Time Minutes Minutes
8953 N119:53 48954 R Current Phase A
Amps8954 N119:54 48955 R Current Phase B
8955 N119:55 48956 R Current Phase C
8956 N119:56 48957 R Heatsink Temperature
Temperature
8957 N119:57 48958 R RTD Temperature
8958 N119:58 48959 R Thermal Capacity Used Percent (%)
8959 N119:59 48960 R Time until Start Minutes
8960 N119:60 48961 R Full Load Amps Amps
8961 N119:61 48962 R Locked Rotor Current Percent (%)
8962 N119:62 48963 R Stall Time Seconds
8963 N119:63 48964 R Jam Current Level Percent (%)
8964 N119:64 48965 R Jam Run Delay Seconds
8965 N119:65 48966 R DBS Service Factor
Percent (%)
8966 N119:66 48967 R Current Unbalance Alarm Level
8967 N119:67 48968 R Current Unbalance Alarm Run Delay Seconds
8968 N119:68 48969 R RTD Temperature Alarm Level
Temperature
8969 N119:69 48970 R RTD Temperature Trip Level
8970 N119:70 48971 R Bypass Time Seconds
8971 N119:71 48972 R Constant Current Level Percent (%)
8972 N119:72 48973 R Ramp Time Seconds
8973 N119:73 48974 R DBS Version Real
8974 N119:74 48975 R Last Trip Current Amps
8975 N119:75 48976 R Last Trip Heatsink Temp
Temperature
8976 N119:76 48977 R Last Trip RTD Temp
8977 N119:77 48978 R Last Trip Thermal Capacity Percent (%)
8978 N119:78 48979 R Last Trip FLA Amps
8979 N119:79 48980 R Last Trip Current Step Percent (%)
8980 N119:80 48981 R Last Trip Ramp Time
Seconds
8981 N119:81 48982 R Last Trip Bypass Time
8982 N119:82 48983 R Last Run Time Hours Hours
8983 N119:83 48984 R Last Run Time Minutes Minutes
8984 N119:84 48985 R Total Accumulated Run Time Hours Hours
8985 N119:85 48986 R Total Accumulated Run Time Minutes Minutes
8986 N119:86 48987 R Total Number of Starts
None
8987 N119:87 48988 R Total Short Circuit Trips
8988 N119:88 48989 R Total Jam Trips
8989 N119:89 48990 R Total Phase Loss Trips
8990 N119:90 48991 R Total Phase Reversal Trips
8991 N119:91 48992 R Total Current Unbalance Trips
8992 N119:92 48993 R Total Heatsink Overtemp Trips
8993 N119:93 48994 R Total RTD Overtemp Trips
8994 N119:94 48995 R Total Thermal Overload Trips
8995 N119:95 48996 R Maximum RTD Temperature Temperature
8997 N119:97 48998 R Locked Rotor Current Setpoint Percent (%)