5-28
SM-18003
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
SettingCondition SettingTemperatureforAutomaticReset
66(19) 66
o
F (19
o
C)
68(20) 68
o
F (20
o
C)
70(21) 70
o
F (21
o
C)
72(22) 72
o
F (22
o
C)
74(23) 74
o
F (23
o
C)
76(24) 76
o
F (24
o
C)
77(25) 77
o
F (25
o
C)(Factory-Setting)
78(26) 78
o
F (26
o
C)
80(27) 80
o
F (27
o
C)
82(28) 82
o
F (28
o
C)
84(29) 84
o
F (29
o
C)
86(30) 86
o
F (30
o
C)
(56) Automatic Reset Time (F4)
Thisfunctionisutilizedtosettheautomaticresettimewiththesettemperature.
Thesettingconditionsandautomaticresettimeareasfollows:
(55) Automatic Reset of Setting Temperature (F3)
Thisfunctionisutilizedtoeconomizetheoperation.Whenthisfunctionisvalid,inthecasethatthe
settemperatureisnotchangedforcertainperiodoftimebythefunction(56)“AutomaticResetTime
(F4)”,thesettemperatureautomaticallyreturnsto(57/58)“AutomaticResetTemperatureforCooling/
Heating(F5/F6)”asfollowingconditions.Itiseffectivetooptimizethesettingtemperatureandprovide
energysaving.However,thesettingtemperatureisnotautomaticallyresetinthecasethat“Automatic
COOL/HEATOperation”mode,or“ProhibitingOperationbyWiredController”issetbythecentralized
controller.
<Example>AutomaticResetTemperatureforCoolingis77
o
F (25
o
C)
(57) Automatic Reset Temperature for Cooling (F5)
ThisfunctionisutilizedtosettheautomaticresettemperatureforFAN/COOL/DRYoperation.
Thesettingconditionsandtheautomaticresettemperatureforcoolingareasfollows:
SettingCondition AutomaticResetTimeofSettingTemperature
00 30minutes(Factory-Setting)
01 15minutes
02 60minutes
03 90minutes
Setting
Temperature Change
Return to (57) Automatic Reset
Temperature for Cooling
Return to (58)
Automatic Reset
Temperature for Heating