EasyManua.ls Logo

Johnson Controls HICM008B21S - Function Setting Details; Cooling Lower Limit for Setting Temperature (FC); Heating Upper Limit for Setting Temperature (Fd)

Johnson Controls HICM008B21S
152 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5-30
SM-18003
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
(64) Cooling Lower Limit for Setting Temperature (FC)
ThisfunctionisutilizedtolimitthelowestsettingtemperatureforFAN/COOL/DRYoperations.
Whenthisfunctionisvalid,itprovidestheappropriatecoolingoperationandenergysaving.
Thesettingconditionsandtheminimumsettingtemperatureforcoolingareasfollows:
<Example>
(65) Heating Upper Limit for Setting Temperature (Fd)
ThisfunctionisutilizedtolimitthehighestsettingtemperatureforHEAToperation.
Whenthisfunctionisvalid,itprovidestheappropriateheatingoperationandenergysaving.
Thesettingconditionsandtheheatingupperlimitforthesettingtemperatureareasfollows:
<Example>
SettingCondition Details
MinimumSettingTemperature
(FAN/COOL/DRY)*
00 StandardValue 66
o
F (19
o
C)
01 LowerLimit+2
o
F(LowerLimit+1
o
C) 68
o
F (20
o
C)
02 LowerLimit+4
o
F(LowerLimit+2
o
C) 70
o
F (21
o
C)
03 LowerLimit+6
o
F(LowerLimit+3
o
C) 72
o
F (22
o
C)
04 LowerLimit+8
o
F(LowerLimit+4
o
C) 74
o
F (23
o
C)
05 LowerLimit+10
o
F(LowerLimit+5
o
C) 76
o
F (24
o
C)
06 LowerLimit+11
o
F(LowerLimit+6
o
C) 77
o
F (25
o
C)
07 LowerLimit+12
o
F(LowerLimit+7
o
C) 78
o
F (26
o
C)
08 LowerLimit+14
o
F(LowerLimit+8
o
C) 80
o
F (27
o
C)
09 LowerLimit+16
o
F(LowerLimit+9
o
C) 82
o
F (28
o
C)
10 LowerLimit+18
o
F(LowerLimit+10
o
C) 84
o
F (29
o
C)
*IncaseofStandardUnit
SettingCondition Details
SettingTemperatureUpperLimit
(HEAT)*
00 StandardValue 86
o
F (30
o
C)
01 UpperLimit-2
o
F(UpperLimit-1
o
C) 84
o
F (29
o
C)
02 UpperLimit-4
o
F(UpperLimit-2
o
C) 82
o
F (28
o
C)
03 UpperLimit-6
o
F(UpperLimit-3
o
C) 80
o
F (27
o
C)
04 UpperLimit-8
o
F(UpperLimit-4
o
C) 78
o
F (26
o
C)
05 UpperLimit-9
o
F(UpperLimit-5
o
C) 77
o
F (25
o
C)
06 UpperLimit-10
o
F(UpperLimit-6
o
C) 76
o
F (24
o
C)
07 UpperLimit-12
o
F(UpperLimit-7
o
C) 74
o
F (23
o
C)
08 UpperLimit-14
o
F(UpperLimit-8
o
C) 72
o
F (22
o
C)
09 UpperLimit-16
o
F(UpperLimit-9
o
C) 70
o
F (21
o
C)
10 UpperLimit-18
o
F(UpperLimit-10
o
C) 68
o
F (20
o
C)
11 UpperLimit-20
o
F(UpperLimit-11
o
C) 66
o
F (19
o
C)
12 UpperLimit-22
o
F(UpperLimit-12
o
C) 64
o
F (18
o
C)
*IncaseofStandardUnit
Factory-Setting: "00"
(Lower Limit 66+0=66
o
F (19+0=19
o
C))
Setting Condition: "06"
(Lower Limit 66+1
1=77
o
F (19+6=25
o
C))
66
o
F
(19
o
C)
86
o
F
(30
o
C)
86
o
F
(30
o
C)
77
o
F
(25
o
C)
Temperature Setting: Available
Setting Temperature at Wired Controller
Temperature Setting
: Not Available
Temperature Setting
: Available
Factory-Setting: "00"
(Upper Limit 86-0=86
o
F (30-0=30
o
C))
Setting Condition: "09"
(Upper Limit 86-16=70
o
F (30-9=21
o
C))
64
o
F
(18
o
C)
86
o
F
(30
o
C)
64
o
F
(18
o
C)
70
o
F
(21
o
C)
Setting Temperature at Wired Controller
Temperature Setting: Available
Temperature Setting
: Not Available
Temperature Setting
: Available

Table of Contents