EasyManua.ls Logo

Johnson Controls HICM008B21S - Function Setting Details; Sensor Installation Position and Louver Control Settings

Johnson Controls HICM008B21S
152 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SM-18003
5-33
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
(94) Not Prepared (L2)
(95) Louver Setting during Energy-Saving Forced Thermo-OFF (L3)
(96) Fan Speed during Energy-Saving Forced Thermo-OFF (L4)
Thisfunctionisutilizedtoincreasethefanspeedtopreventthedeteriorationofcomfortduetoforce
thermo-OFFforenergysavingduringcoolingoperation.
SettingCondition AirVolumeDuringForceThermo-OFF
AirFlowVolume HIGH2 HIGH MED LOW
00(Standard) HIGH2 HIGH MED LOW
01(HiSpeed) HIGH2 HIGH2 HIGH MED
SettingCondition Energy-SavingForceThermo-OFF
00(ReceiveAir:LOW) LouverstayindownwardairowpositionduringAutoSwingMode
01(ReceiveAir:MED) Louverstayindownwardairowpositionlongerthan"00"duringAutoSwingMode
02(ReceiveAir:HIGH) Louverisxedatthe7thstepofdownwardairow
03(NotAvailable) Cancelthelouveroperation
(93) Motion Sensor Installation Position (L1)
Thisfunctionisutilizedtoselecttheinstallationpositionofthecoverforcornerwithmotionsensorand
radiationtemperaturesensorbywiredcontroller.
SettingCondition Installation Position
00 A(Factory-Setting)
01 B
02 -(NotAvailable)
03 D
Ref.
Pipe
Mark of
Mark of
Mark of
Mark of
Mark of
The motion sensor cannot
install to the location of the mark of “C” .
B
C
A
The mark of “A” is
the factory setting position
for motion sensor.
D
Electrical Box
Decorative Panel without
Four Corner Covers
(97) Louver Swing Operation during Energy-Saving Forced Thermo-OFF (L5)
Thisfunctionissetat"01",thefunction"L3"settingwillbeavailable.
(98) Not Prepared (L6)
(99) Not Prepared (L7)
(100) Not Prepared (L8)
(101) Not Prepared (L9)
(102) Not Prepared (LA)
(103) Not Prepared (Lb)
(104) Setting Temperature (P1)
Thisfunctionisutilizedtoprovidesettingtemperatureforevery1
o
F (0.5
o
C)at"00"andevery2
o
F (1
o
C)
at"01".
Controldifferentialofthermistoralsousesthetemperatureforevery1
o
F (0.5
o
C)at"00"andevery2
o
F
(1
o
C)at"01".
(105) Not Prepared (P2)
(106) Thermistor Selection (P3)
Thisfunctionisutilizedtoselectthethermistorwithfunction(107).
SettingCondition Thermistor(Sensor)
00 InletAirThermistor
01 OutletAirThermistor
02 ThermistorofRemoteControl
03 RemoteSensor