5-34
SM-18003
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
(107) Display of Thermistor Temperature (P4)
Thisfunctionisutilizedtodisplaythetemperatureofthesensorselectedat(106).
(108) Setting Temperature Display during Fan Operation (P5)
Thisfunctionisutilizedtoundisplaythesettingtemperatureduringfanmodeoperation.
(109) ECO Button Operation (P6)
Thisfunctionisprohibiting"ECO"buttonoperationbysettingat"01"
(110) Menu Button Operation (P7)
Thisfunctionisutilizedtoinvalidatethemenubutton.
(111) Not Prepared (P8)
(112) Not Prepared (P9)
(113) Not Prepared (PA)
(114) Not Prepared (Pb)
(115) Not Prepared (PC)
(116) Not Prepared (q1)
(117) Not Prepared (q2)
(118) Not Prepared (q3)
(119) Not Prepared (q4)
(120) Not Prepared (q5)
(121) Not Prepared (q6)
(122) Not Prepared (q7)
(123) Not Prepared (q8)
(124) Not Prepared (q9)
(125) Not Prepared (qA)
(126) Not Prepared (qb)
(127) Not Prepared (qC)
(128) Not Prepared (qd)
(129) Dual Setpoint (for Automatic COOL/HEAT Operation) (r1)
Thisfunctionisutilizedtoactivate/deactivatedualsetpointofcoolingandheatinginautomaticcooling
andheatingoperation.
Thisfunctionisinvalidwhenthefunctionof"AutomaticCOOL/HEATOperation"isinvalid.
(130) Cooling/Heating Changeover Temperature (for Automatic COOL/HEAT Operation) (r2)
ThisfunctionisutilizedtochangetheindoortemperatureconditiontoThermo-ON/OFF.
Thisfunctionisinvalidwhenthefunctionof"DualSetpoint"isinvalid.
Incasedualsetpointisselectedinautomaticheating/coolingoperation,duringautomodebothcooling
setpointandheatingsetpointcanbeselected.
Bydefault,temperaturewhentheheating/coolingmodechangesareasfollows.
Coolingmodechangestoheatingmodewhentheindoortemperatureisheatingsetpoint-2
o
F
(-1
o
C
).
Heatingmodechangestocoolingmodewhentheindoortemperatureiscoolingsetpoint+2
o
F
(+1
o
C
).
SettingCondition ActualControlTemperature
00(Standard) 2
o
F (1.0
o
C)
01 3
o
F (1.5
o
C)
02 3
o
F (2.0
o
C)
03 4
o
F (2.5
o
C)
04 5
o
F (3.0
o
C)
05 1
o
F (0.5
o
C)

Table of Contents