SM-18003
5-35
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
(132) Not Prepared (r4)
(133) Not Prepared (r5)
(134) Not Prepared (r6)
(135) Not Prepared (r7)
(136) Not Prepared (r8)
(137) Not Prepared (r9)
(138) Not Prepared (rA)
(139) Not Prepared (rb)
(140) Not Prepared (S1)
(141) Not Prepared (S2)
(142) Not Prepared (S3)
(143) Not Prepared (S4)
(144) Not Prepared (S5)
(145) Not Prepared (S6)
(146) Not Prepared (S7)
(147) Not Prepared (S8)
(131) Setback Temperature Compensation (During card key removal, setpoint is setbacked) (r3)
ThisfunctionisutilizedtochangetheindoortemperatureconditiontoThermo-ON/OFF.
Incasethesetbackoperationisenabledandthecardkeyisremoved,setpointiscompensatedand
fanoperateat“LOW”speed.
Bydefault,
Cooling:Setpoint+4
o
F
(+2.5
o
C
)
Heating:Setpoint-4
o
F
(-2.5
o
C
)
Whentheexternalsignalisdetected(cardkeyisinserted),returntotheoriginalsettingtemperature.
SettingCondition ActualControlTemperature
00(Standard) WiredControllerSettingTemperature(IndicatedValue)+4
o
F (2.5
o
C)
01 WiredControllerSettingTemperature(IndicatedValue)+5
o
F (3.0
o
C)
02 WiredControllerSettingTemperature(IndicatedValue)+6
o
F (3.5
o
C)
03 WiredControllerSettingTemperature(IndicatedValue)+7
o
F (4.0
o
C)
04 WiredControllerSettingTemperature(IndicatedValue)+8
o
F (4.5
o
C)
05 WiredControllerSettingTemperature(IndicatedValue)+9
o
F (5.0
o
C)
06 WiredControllerSettingTemperature(IndicatedValue)+10
o
F (5.5
o
C)
07 WiredControllerSettingTemperature(IndicatedValue)+1
o
F (0.5
o
C)
08 WiredControllerSettingTemperature(IndicatedValue)+2
o
F (1.0
o
C)
09 WiredControllerSettingTemperature(IndicatedValue)+3
o
F (1.5
o
C)
10 WiredControllerSettingTemperature(IndicatedValue)+3
o
F (2.0
o
C)
Compensationforsetbackoperationcanbechangedasshowninthetablebelow.